Skip to Main Content
Need Support? Let’s guide you to the right answer or agent.
Status Future consideration
Created by Guest
Created on Apr 27, 2026

Return the load factors for the TU load case to 0.5 min & 0.5 max in LEAP Bridge Concrete

It is too conservative and unnecessary to use a 1.2 load factor for the TU load case for design/analysis of substructures. The 1.2 load factor is only needed when calculating thermal movement for joints, expansion devices, and bearings as stated in AASHTO LRFD 10th Edition page 3-13. Using a max TU load factor of 1.2 along with a min TU load factor of 0.5 also unnecessarily doubles the load combinations which increases the time needed to run the design and analysis.

Civil Product Used OpenBridge Designer
  • ADMIN RESPONSE
    May 4, 2026

    I agree that the max load factor 1.2 should not be used for force effects when evaluating the strength/service limit states. However, using load factor 0.5 could lead to an unexpected less conservative design if the partial cracked moment of inertial is considered. So, I suggest using the default max load factor 1.0 and min load factor 0.5 for the strength limit states. Please let me know if this works for you.